- For Europe: CENELEC / ATEX Directive
|
|
|
-
|
|
|
Gas
Group |
|
|
|
-
|
| Temperature |
|
|
|
|
Typical
material |
Apparatus
group |
|
|
Max.
surface
temperature
|
- T-
Class
|
Classification |
|
|
|
| ATEX |
|
|
|
-
|
- Methane
|
- I
Mining
(M1/M2)
|
-
|
|
- 450°C
|
- T1
|
|
|
-
|
|
- Propane
|
- IIA
|
-
|
|
- 300°C
|
- T2
|
CE
Marking Directive |
Basic
requirements |
-
|
- Ethylene
|
- IIB
Surface
|
-
|
|
- 200°C
|
- T3
|
Low
Voltage Directive |
Electrical safety of equipment, voltage
ranges 50-1000AC, 75-1500 DC
|
|
- Hydrogen
|
IC
Applications
|
-
|
|
- 135°C
|
- T4
|
EMC
Directive |
- Electromagnetic emissions and immunity
|
-
|
- Acetylene
|
- IIC
|
-
|
|
- 100°C
|
- T5
|
Machinery
Directive |
- Mechanical and electrical safety
|
-
|
- All
Gases
|
- II
|
-
|
|
- 85°C
|
- T6
|
Atex
Directive |
- Hazardous Area Equipment (mandatory form 1st July
2003 Currently accepted
|
-
EEx
ed IIB
T4
|
 II
1 G |
| ****
4 Digit body number |
-
|
- Protection
Concepts
|
- Symbol
|
- Zone
|
- Standard
|
- How it works
|
Category
|
-
|
- Increased
Safety
|
- Ex
e
|
- 1 & 2
|
- EN
50019
|
- No
arcs, sparks or hot surfaces
|
2
|
-
|
- Non-sparking
|
- Ex
nA
|
- 2
|
- EN
50021
|
3
|
-
|
- Flameproof
|
- Ex
d
|
- 1 & 2
|
- EN
50018
|
- Contain
the explosion and quench flame
|
2
|
-
|
- Enclosed
Break
|
- Ex
nW
|
- 2
|
- EN
50021
|
3
|
-
|
- Quartz/Sand
Filled
|
- Ex
q
|
- 1 & 2
|
- EN
50017
|
2
|
-
|
- Intrinsic
Safety
|
-
Ex ia
- Ex
ib
|
- 0,1 & 2
- 1 & 2
|
- EN
50020
- EN
50039
|
- Limit
energy of sparks; limit the temperature
|
- 1
-
- 2
-
- 3
|
-
|
- Energy
Limitation
|
- Ex
nL
|
- 2
|
- EN
50021
|
-
|
- Pressurised
|
- Ex
p
|
- 1 & 2
|
- EN
50016
|
- Keep
the flammable gas away from any hot surfaces and ignition
Capable
equipment
-
|
2
|
-
|
- Simplified
Pressurisation
|
- Ex
nP
|
- 2
|
- EN
50021
|
3
|
-
|
- Encapsulation
|
- Ex
m
|
- 1 & 2
|
- EN
50028
|
2
|
-
|
- Oil
Immersion
|
- Ex
o
|
- 1 & 2
|
- EN
50015
|
2
|
-
|
- Restricted
breathing
|
- Ex
nR
|
- 2
|
- EN
50021
|
3
|
-
|
- Special
|
- Ex
s
|
- 0*,1&2
|
- EHSR
(ATEX)
|
- Any Proven Method
|
1, 2 & 3
|
|
|
|
- * Label must indicate Zone 0
|
|
|
|
Classification |
Criteria
For Zone |
ATEX Marking
|
|
|
Zone
0 |
Flammable
material always present or for long periods (e.g.1000 hours or more per
year) |
G |
Category
1
Equipment |
|
|
Zone
20 |
D |
|
|
Zone
1 |
Flammable
material present in normal operation (e.g. 10-1000 hours/year) |
G |
Category
2
Equipment |
|
|
Zone
21 |
D |
|
|
Zone
2 |
Flammable
material present for short periods only (e.g. less than 10 hours/year) |
G |
Category
3
Equipment |
|
|
Zone
22 |
D |
|
- For North America
|
- PROTECTION
METHODS
INTRINSICALLY SAFE
Ex ia IIC T4
(Method of protection)
Class I, Division 1
(Area Classification)
Groups A, B, C and D
(Gas Grouping)
T4
(Temperature Code)
|
- North
America
|
- Method
of
Protection
|
- Division
|
- Intrinsic
Safety
|
- 1
or 2
|
- Explosion-Proof
|
- 1
or 2
|
- Pressurization
|
- 1
or 2
|
- Non-Incendive
Circuits
|
- 2
|
- *Specifically
Assessed
Equipment
|
|
- North
America, CENELEC (Europe) and IEC (International)
|
- Method
of Protection
|
- Zone
|
- Code
Letter
CENELEC/IEC
|
- Intrinsic
Safety
|
- 0,
1 or 2
|
- ia
|
- 1
or 2
|
- ib
|
- Flame-Proof
|
- 1
or 2
|
- d
|
- Pressurization
|
- 1
or 2
|
- p
|
- Increased
Safety
|
- 1
or 2
|
- e
|
|
- (*No
excessive Heat Generating Devices or Ignition-capable
Arcing / Sparking Devices)
|
|
-
|
- AREA
CLASSIFICATION
|
-
|
-
|
- CONTINUOUS
HAZARD
|
- INTERMITTENT
HAZARD
|
- HAZARD
UNDER
ABNORMAL CONDITIONS
|
- NORTH
AMERICA
(CEC/NEC)
|
- Division 1
|
- Division 2
or Zone 2
|
- Zone 0
|
- Zone 1
|
- CENELEC/IEC
|
- Zone 0
|
- Zone 1
|
- Zone 2
|
|
-
|
-
- HAZARDOUS
LOCATIONS GAS GROUPS
|
-
|
- TYPICAL
GAS HAZARD
|
- NORTH
AMERICA
CEC SECTION 18, NEC ARTICLE 500
|
- CENELEC/IEC
CENELEC, EN 50014,
IEC 79-0
|
- ACETYLENE
|
- A or IIC
|
- IIC
|
- HYDROGEN
|
- B or IIC
|
- IIC
|
- ETHYLENE
|
- C or IIB
|
- IIB
|
- PROPANE
|
- D or IIA
|
- IIA
|
- METHANE
|
- Group D (gaseous
mines) or I
|
- I
|
|
-
|
-
- TEMPERATURE
CODE/CLASS
|
-
|
- MAXIMUM
SURFACE TEMPERATURE (°C)
|
- 450
|
- 300
|
280 |
260 |
230 |
215 |
- 200
|
180 |
165 |
160 |
- 135
|
120 |
- 100
|
- 85
|
- NORTH
AMERICA
Temp Code
|
- T1
|
- T2
|
T2A |
T2B |
T2C |
T2D |
- T3
|
T3A |
T3B |
T3C |
- T4
|
T4A |
- T5
|
- T6
|
- CENELEC/IEC
Temp Class
|
- T1
|
- T2
|
- T3
|
- T4
|
- T5
|
- T6
|
|
|